Overview:
(The values in this table are edge-values for the resp. type range. The adjustment range for the power supplies usually is beginning from zero.)

Power supply type range

Design principle

Vmin
Volts
Vmax
Volts
Imin
Amps
Imax
Amps
Pmin
Watts
Pmax
Watts

NCA (floating output)

Switch mode power supply

55 55 40 160 750 3000
MCA (floating output)

Switch mode power supply

150 3000 0,75 180 750 9000
 
 
Series NCA/MCA ...

Printer friendly data sheet (PDF)

Features:

  • Autoranging characteristic with constant power limitation
  • 5 power classes: from 750 W to 9 kW
  • 6 Voltages: 55 V to 3000 V
  • Up to 1500V with floating output 
  • Compact size (19" case)
  • Light-weight
  • High efficiency
  • Short-circuit proof
  • Unlimited operation with nominal power (even in short-circuit conditions)
  • Voltage and current regulation with automatic, sharp transition and additional power limitation
  • Control mode indicated by LED
  • Voltage and current setting with10-turn potentiometers with precision scale; the adjusting knob can be locked
  • 4½ digit DVM for voltage and current
  • Suitable also for capacitive loads
  • Sense connections to compensate voltage drop at the load cables for NCA
  • Active down control for NCA

to top of the page

Function:

The NCA/MCA series is an autoranging power supply design in which the power supplies operate over the full range of their output voltage & current - up to the units maximum rated output power. This results in an operating range which is up to 3-times wider than that of a more conventional power supply. When fitted with one of the optional interfaces (IEEE 488, USB, Ethernet and others), the MCA/NCA series become versatile programmable power supplies.

In principle, the rectified line voltage drives a square wave generator of variable frequency, whose AC voltage is transformed, rectified and filtered, producing the output voltage. For regulation, the square wave voltage is pulse width modulated.

Design:

Output:

  • Output isolation:
    up to 1500 V nominal voltage the output is floating. Either the positive or the negative pole may be connected to earth.

    (Not valid with the option analogue programming. If the floating function should remain, the floating analogue programming must be chosen).

    Maximum isolation voltage:
    up to 400 V nominal voltage:
    at 750 V nominal voltage: 
    at 1500 V nominal voltage:
    at 3000 V nominal voltage:
    ±500 V.
    ±1000 V
    ±2000 V
    one pole is earthed, the polarity must be indicated when ordering.
  • Output terminals:
    Units up to 750 V nominal voltage have 4mm safety connectors.
    From 1500 V nominal voltage on SHV connectors are provided. HV-cable connectors are included.
    Units from 24 A nominal current on have binding posts.

Technical Data:

  • Mains connection: 
    Up to 1500 W nominal power 230 V ±10% 47 Hz to 63 Hz;
    For nominal power 3000 W and higher 400 V ±10% 47 Hz to 63 Hz 3-phase
  • Ambient temperature: 0°C to +40°C

 

  • The following data applies for voltage and current regulation, and refers to the rated value (if not stated otherwise):
    (For explanations please refer to the Terms & Definitions page.)

    Setting range: 

    from approx. 0,1% to 100%

    Reproducibility:

    ±1 x 10-4

    Setting resolution (potentiometer): 

    ±1 x 10-3

    Residual ripple:

    <2 x 10-4pp + 200 mVpp

    Recovery time:
    Voltage control:
    Current control:

    <1 ms for load changes from 10% to 100% or from 100% to 10%.
    <10 ms for load changes causing an output change of less than 10% of the rated voltage

    Setting time at nominal load:

    <300 ms for changes of the output voltage from 10% to 90% or 90% to 10%

    Discharging time constant
    for output without load:


    approx. 10 sec.

    Deviation: 
    for ±10% mains voltage variation:
    for no load / full load:
    over 8 h under constant conditions:
    within the temperature range:


    ± 1 x 10-5
    <5 x 10-4
    <±2 x 10-4
    <±1 x 10-4 / K

    Possible Options:

  • Analogue programming
  • Analogue programming, floating
  • DVM with higher resolution
  • Computer interface - IEEE 488, RS 232, RS 422, USB, LAN (Ethernet), Profibus DP (more on request)

    More options and special solutions on request. Some options may involve changes to the description of the unit - especially concerning the mechanical design.

NCA/ MCA Data Sheet:

Zur Darstellung muss der ADOBE READER installiert werden!

 

to top of the page

For prices please ask us or one of our representatives.

 

Please don't hesitate to contact us, if you don't find for what you are searching. We will be happy, to offer a solution, tailored especially to your needs.

Examples for customer specific solutions

to top of the page

zur deutschen Version

 03.05.10 12:56

Impressum - Legal Notice: 

Diese Seite wird betrieben von der FuG Elektronik GmbH, Florianstraße 2, 83024 Rosenheim.
Geschäftsführer: Dr. Hartmut Simon (Vorsitz), Anton Elsasser, Gerhard Huber.
Telefon +49 8031 2851 0
Telefax +49 8031 81099
Registergericht: Traunstein HRB 8638, Umsatzsteuer-Ident-Nr: DE 16 18 91 071.

This page is managed by the FuG Elektronik GmbH, Florianstrasse 2, 83024 Rosenheim (Germany).
Board of Directors: Dr. Hartmut Simon (CEO), Anton Elsasser, Gerhard Huber.
Telephone +49 8031 2851 0
Telefax +49 8031 81099
Commercial court: Traunstein HRB 8638, VAT NR: DE 16 18 91 071.

Mit Anregungen und Hinweisen zu diesen Seiten wenden Sie sich bitte an :
With your suggestions or comments concerning this pages please contact:
webmaster@fug-elektronik.de 

Trotz sorgfältiger inhaltlicher Kontrolle übernehmen wir keine Haftung für die Inhalte externer Links. Für den Inhalt der verlinkten Seiten sind ausschließlich deren Betreiber verantwortlich. (siehe auch HAFTUNGSAUSSCHLUß)
In spite of thorough check of the contents we do not take over any liability for the contents of external links. For contents of linked websites are responsible  exclusively the persons who running them. (see NON LIABILITY STATEMENT- disclaimer)

Stand: 23. Januar 2009
©
FuG Elektronik GmbH